Safety Requirements For Explosion-Proof Fans

Sep 07, 2026 ご伝言

a) The flameproof motor and associated electrical accessories used with the fan must comply with the provisions of GB 3836.1, GB 3836.2, GB 3836.3, and JB/T 7565.5.

b) Appropriate locations on the surfaces of the fan casing and transmission components must be equipped with grounding devices that meet explosion-proof requirements and bear permanent grounding marks.

c) When the fan's inlet chamber is directly open to the atmosphere, a fixed protective grille (or mesh) must be installed to prevent foreign objects from being drawn into the fan. The structural design of the protective grille (or mesh) must consider factors such as fan size and the operating environment, while also ensuring minimal airflow resistance caused by its installation.

 

d) Rotating (or transmission) components-such as transmission assemblies, couplings, pulleys, and belts-must be equipped with safety guards that comply with GB/T 19074. The guards must be structurally robust and designed to avoid contact with rotating parts. To prevent static electricity accumulation and spark generation, guards that are electrically insulated from the casing must be equipped with a reliable grounding device.

e) Rotating components of the fan must be securely fastened, with measures in place to prevent loosening (e.g., locking the impeller to the shaft; using positioning measures for bearing pedestals, bearing housings, and the motor relative to the support frame).

f) Where the impeller shaft passes through the fan casing, an aluminum sealing/isolation ring with a locating shoulder must be installed at the shaft opening in the steel casing; the radial clearance (gap on one side) between the inner bore of the sealing ring and the shaft must be 0.5 mm.